10kV PT柜送电过程电压异常及N600接线烧焦案例分析

Case Analysis of Voltage Abnormalities During 10kV PT Cabinet Power Supply and Charred N600 Wiring

  • 摘要: 本案例分析一起某110kV变电站在10kVⅢ段母线PT柜改造工程结束后的送电过程中,出现一次消谐本体单相击穿,二次微机消谐装置损坏,10kVⅢ段母线电压异常及电压公用屏N600接线在端子排处烧焦破皮的事件。文章从设备结构、故障前后三相对地电压变化、电流流向等方面入手,结合故障现象展开分析,并提出解决方案与反思。

     

    Abstract: This case analysis focuses on an incident that occurred during the power transmission process of a 110kV substation after the completion of the renovation project for the 10kV III section busbar PT cabinet. During this process, there was a single-phase breakdown of the harmonic suppression unit, damage to the secondary microcomputer harmonic suppression device, abnormal 10kV III section busbar voltage, and burning and peeling of the N600 wiring on the voltage common panel at the terminal block. The article starts from aspects such as the equipment structure, changes in the three-phase-to-ground voltages before and after the fault, and the current flow direction, and conducts an analysis based on the fault phenomenon. It also proposes solutions and reflections.

     

/