燃煤机组厂用10kV母线电压互感器高压熔断器慢熔故障分析与在线处置

Slow-melting Fault Analysis and On-site Online Disposal of High-voltage Fuse for 10kV Bus Voltage Transformer in Coal-fired Power Units

  • 摘要: 电压互感器(PT)一次侧高压熔断器慢熔是燃煤机组厂用电系统中较为隐蔽的异常工况,其故障相二次电压下降幅度小、持续时间长,常规PT断线判据难以可靠识别,易导致低电压保护误动或厂用快切装置异常动作。针对某燃煤机组1号机组厂用10kV B段母线PT A相高压熔断器慢熔故障,本文分析了故障发生时的二次电压不对称特征,对比了慢熔与单相接地、PT完全断线的电气量差异,阐述了熔断器慢熔的物理过程与诱因。在此基础上,制定并实施了不停机在线更换熔断器的处置方案,给出了退出相关保护与自动装置、测量熔断器绝缘电阻、三相统一更换及恢复送电的完整步骤。更换前后熔断器导通电阻与绝缘电阻的对比验证了故障定位的准确性。最后从熔断器选型、定期检测、保护逻辑优化和运行监视四个方面提出了防范措施,可为同类型厂用母线PT慢熔故障的处置提供参考。

     

    Abstract: The slow-melting fault of the primary-side high-voltage fuse of voltage transformer (PT) is a relatively concealed abnormal working condition in the auxiliary power system of coal-fired power units. The faulty phase presents a slight and long-term drop in secondary voltage, which cannot be reliably identified by conventional PT disconnection criteria, and may easily cause mal-operation of low-voltage protection and abnormal action of the auxiliary power fast switching device. Aiming at the A-phase slow-melting fault of the high-voltage fuse for the PT on the 10kV B-section bus of Unit 1 in a coal-fired power unit, this paper analyzes the asymmetric characteristics of secondary voltage during the fault, and compares the electrical parameter differences among slow-melting fault, single-phase grounding fault and complete PT disconnection fault. The physical process and inducing factors of fuse slow-melting are elaborated. On this basis, an online fuse replacement scheme without unit shutdown is formulated and implemented, and the complete disposal procedures are proposed, including exiting relevant protection and automatic devices, measuring fuse insulation resistance, uniformly replacing three-phase fuses and restoring power supply. The comparison of conduction resistance and insulation resistance of fuses before and after replacement verifies the accuracy of fault location. Finally, preventive measures are put forward from four aspects including fuse type selection, regular detection, protection logic optimization and operational monitoring, which can provide a reference for the disposal of similar PT slow-melting faults of auxiliary power buses.

     

/

返回文章
返回