高级检索

某水电站 AGC 自动穿越振动区控制策略优化研究

Research on Optimization of AGC Automatic Vibration Zone Crossing Control Strategy for a Hydropower Station

  • 摘要: 朱帅:本文通过对大型水电站AGC穿越振动区控制策略开展研究,针对电站原固定步长、单机优先分配策略存在的出力偏差超限、AGC易强制退出等问题,优化提出多机组协同负荷分摊控制方法,并通过现场试验对优化策略进行验证。结果表明,该方法可有效压缩机组出力偏差、消除AGC误退出隐患,保障机组平稳快速穿越振动区,显著提升水电站及电网调度运行的安全稳定性。

     

    Abstract: This paper investigates the automatic generation control (AGC) strategy for vibration zone crossing in large-scale hydropower stations. Aiming at the problems of excessive active power deviation and forced AGC exit caused by the fixed-step and single-unit priority load distribution adopted in the original control strategy, a multi-unit cooperative load sharing control method is proposed. Field tests are carried out to verify the optimized strategy. The results show that the proposed method can effectively reduce the unit active power deviation, eliminate the hidden danger of accidental AGC exit, ensure stable and fast vibration zone crossing of generating units, and significantly improve the operational safety and stability of hydropower stations and power grid dispatching.

     

/

返回文章