高级检索

一起500kV电容式电压互感器选择开关故障分析

Analysis of a 500kV capacitive voltage transformer selection switch fault

  • 摘要: 对一起500 kV电容式电压互感器(capacitive voltage transformer,CVT)投运后,二次系统电压为零事件开展分析。经由实际测量二次线圈电压,将故障确定为电容式电压互感器(CVT)本体故障。停电后对CVT进行介损电容量试验,判断由于CVT出厂时将选择开关位置标示标反,投运前将选择开关误拨至“试验”位置,中间变压器首端接地,二次线圈电压归零是该事故的直接原因。最后归纳了选择开关位置的确定方法,并提出相应的防范措施。

     

    Abstract: An analysis was conducted on an incident where the secondary system voltage of a 500 kV capacitive voltage transformer (CVT) was zero after being put into operation. Through actual measurements of the secondary coil voltage, the fault was determined to be a fault in the CVT itself. After the power outage, a dielectric loss and capacitance test was conducted on the CVT. It was determined that the direct cause of the incident was that the selection switch position was marked reversely when the CVT was shipped, and the selection switch was mistakenly set to the "test" position before being put into operation. The primary terminal of the intermediate transformer was grounded, causing the secondary coil voltage to return to zero. Finally, the method for determining the position of the selection switch is summarized, and corresponding preventive measures are proposed.

     

/

返回文章
返回