基于单相dq变换的分相限流控制策略

A Phase-Wise Fault Current-Limiting Strategy for Grid-Forming Inverters Based on Single-Phase dq Transformation

  • 摘要: 针对VSG型构网逆变器在不对称故障下三相dq等比例限流难以分相约束电流、单相虚拟阻抗缺少直接电流限制的问题,提出基于单相dq变换的分相限流策略。该策略以VSG相角为投影基准,分别提取三相电压和逆变器侧电流基波信息,由各相电压外环独立生成并直接限制电流参考。基于15 kW模型,在四类故障下与无限流及上述两种限流策略对比。AB故障下,其稳态电流峰值为70.5 A,低于三相dq限流的76.5 A和虚拟阻抗限流的76.4 A;故障后稳态有功功率标准差为0.025 kW,低于两者的0.226 kW和0.253 kW。结果表明,该策略提高了不对称故障下的分相限流能力,并减小了故障后稳态有功功率波动。

     

    Abstract: Conventional three-phase dq proportional current limiting cannot constrain individual phase currents under asymmetrical faults, while per-phase virtual-impedance limiting regulates fault current only indirectly. To address these limitations, a phase-wise current-limiting strategy based on single-phase dq transformation is proposed for VSG-controlled grid-forming inverters. Using the VSG angle as a common projection reference, the strategy extracts each phase’s fundamental voltage and inverter-side current components, enabling independent generation and direct limitation of phase current references. A 15-kW model compares the proposed strategy with a VSG controller without current limiting and the two conventional limiters under four fault conditions. Under an AB fault, the proposed strategy limits the steady-state peak current to 70.5 A, compared with 76.5 A and 76.4 A for the two conventional limiters. The post-fault steady-state active-power standard deviation is 0.025 kW, lower than their respective values of 0.226 kW and 0.253 kW. These results indicate improved phase-wise current limiting under asymmetrical faults and reduced post-fault steady-state active-power fluctuations.

     

/