一起因同杆架设线路连续故障导致的110kV主变跳闸事件分析与处理
Analysis and handling of the 110kV main transformer trip incident caused by continuous faults on lines erected on the same pole
-
摘要: 某110kV变电站在2号主变大修期间发生某10kV线路跳闸后,3号主变低后备继续动作,依次跳开低压侧分段930断路器和低压侧903断路器,造成10kVII母、10kVIII母失电,负荷损失1.12万千瓦。为查找故障原因,首先排查其他10kV线路保护装置是否存在告警及动作情况,其次检查主变保护定值录入正确情况,最后进行10kV线路保护及主变后备保护动作情况以及故障录波图像分析。最后分析得出该起故障由两条同杆架设的10kV线路连续相继发生故障,故障时间超过3号主变低后备保护时间定值,导致主变跳闸。Abstract: During the major overhaul of the No. 2 main transformer at a certain 110kV substation, after a trip of a certain 10kV line occurred, the No.3 main transformer low backup protection continued to operate, sequentially tripping the low-voltage side sectionalising circuit breaker 930 and the low-voltage side circuit breaker #903, causing the 10kVII bus and 10kVIII bus to lose power, resulting in a load loss of 11,200 kW. To determine the cause of the fault, other 10kV line protection devices were first checked for any alarms or operations, followed by verification of the correct input of main transformer protection settings, and finally analysis of the 10kV line protection and main transformer backup protection operations as well as fault waveform recordings. It was ultimately concluded that the fault was caused by two 10kV lines installed on the same pole experiencing consecutive faults, with the fault duration exceeding the time setting of the No. 3 main transformer low backup protection, leading to the transformer tripping.