含分布式电源的配电网多端同步测量小电流接地定位策略

Multi-terminal Synchronous Measurement Strategy for Low Current Ground Fault Location in Distribution Networks with Distributed Power Sources

  • 摘要: 针对高比例分布式电源(DG)并网导致配电网故障特征复杂、传统定位方法耐受高阻及通信扰动能力不足的难题,提出一种基于多端同步测量与图卷积网络的小电流接地故障定位策略。该方法构建考虑锁相环动态特性的逆变型DG诺顿等效模型,量化弱馈电流对序网参数的影响;采用IEEE 1588v2透明时钟技术结合滑动窗口时标校正,实现恶劣通信环境下的微秒级硬同步;利用广义S变换提取暂态零序能量谱,经核主成分分析降维后映射为图节点属性,输入双层图卷积网络挖掘拓扑空间相关性以实现故障区段辨识。硬件在环测试表明,该策略在1000Ω高阻接地及30%丢包率的极端工况下仍保持90%以上的定位成功率,且端到端延时满足配电自动化速动性要求。

     

    Abstract: To address the challenges of complex fault characteristics in distribution networks caused by high penetration of distributed generation (DG) and the insufficient tolerance of traditional fault location methods to high-impedance and communication disturbances, a small-current grounding fault location strategy based on multi-terminal synchronous measurement and graph convolutional networks is proposed. This method constructs an inverter-type DG Norton equivalent model considering the dynamic characteristics of phase-locked loops to quantify the impact of weak-fed current on sequence network parameters. It employs IEEE 1588v2 transparent clock technology combined with sliding window time-stamp correction to achieve microsecond-level hard synchronization in harsh communication environments. By extracting transient zero-sequence energy spectra using generalized S-transform and mapping them to graph node attributes after dimensionality reduction via kernel principal component analysis, the strategy inputs a two-layer graph convolutional network to mine topological spatial correlations for fault section identification. Hardware-in-the-loop tests demonstrate that the strategy maintains over 90% location success rate under extreme conditions such as 1000Ω high-impedance grounding and 30% packet loss rate, while meeting the rapid-response requirements of distribution automation with end-to-end delay compliance

     

/

返回文章
返回