影响接地阻值增大的因素及减小阻值的分析

Factors That Increase Grounding Resistance and Analysis on How to Reduce It

  • 摘要: 接地装置是保障野外物探设备与工业电气系统可靠运行、防范人身触电风险的核心基础设施。针对现场接地电阻检测中普遍存在的数据异常波动、阻值偏大及测量失真问题,首先阐述接地电阻的构成与检测原理,进而从检测操作、土壤特性、环境干扰、引线接触、施工质量5个维度,系统分析接地电阻测量误差增大、真实阻值超标的各类诱因。在此基础上,分别从检测精度控制与工程降阻改造两方面提出优化措施,并结合新疆戈壁地区物探仪器房接地整改实例开展应用验证。结果表明,深井接地与降阻剂组合方案可有效降低高土壤电阻率区域的接地阻值,且季节稳定性优异。研究成果可为同类野外工况下接地系统的检测、运维与整改提供工程参考。

     

    Abstract: Grounding systems are the core infrastructure to ensure the reliable operation of field geophysical survey equipment and industrial electrical systems, as well as to prevent the risk of electric shock to personnel. In response to common issues during on-site grounding resistance testing, such as abnormal data fluctuations, excessive resistance values, and measurement distortions, this paper first explains the composition and testing principles of grounding resistance. It then systematically analyzes various factors leading to increased measurement errors and actual resistance exceeding standards from five aspects: testing operations, soil characteristics, environmental interference, lead connections, and construction quality. Based on this analysis, optimization measures are proposed from the perspectives of testing accuracy control and engineering resistance reduction renovations, and an application verification is conducted using a grounding rectification case for a geophysical instrument room in the Gobi region of Xinjiang. Results indicate that the combination of deep well grounding and resistivity-lowering agents can effectively reduce grounding resistance in areas with high soil resistivity and demonstrates excellent seasonal stability. The research findings can provide engineering references for the testing, operation, maintenance, and rectification of grounding systems under similar field conditions。

     

/

返回文章
返回