高级检索

1000千伏安兰II线第一套线路保护电流回路异常分析

Analysis of the first set of line protection current circuit anomaly of the 1000 kV Anlan II line

  • 摘要: 电流回路异常是导致特高压变电站保护误动的主要原因之一。本文系统分析了1000kV兰江站安兰II线第一套分相电流差动保护(PCS-931GMM)电流回路异常事件。针对保护频繁启动、B、C相采样电流幅值偏小且相位偏移等异常现象,通过多装置数据比对、红外测温、波形向量分析及现场电流校验等方法,精准定位到T032开关汇控柜内9SD大电流切换端子B、C相间高阻短接故障。查明故障原因为端子螺丝孔内残留螺纹铜丝及积污,导致B、C相间经高阻放电。分析了操作频次过高、铜材质特性及制造工艺缺陷等导致残留铜丝的关键因素,提出了针对性的运维改进措施及反事故对策。研究成果可为特高压变电站二次回路隐患排查及大电流端子的运维管理提供重要的参考。

     

    Abstract: Abnormalities in current circuits are one of the primary causes of false tripping in UHV substation protection systems. This paper systematically analyzes an incident involving an abnormal current circuit in the first phase-separated current differential protection (PCS-931GMM) unit for the Anlan II Line at the 1000 kV Lanjiang Substation. In response to abnormal phenomena such as frequent protection tripping, low amplitude of B and C phase sampling currents, and phase shifts, the analysis employed methods including multi-device data comparison, infrared temperature measurement, waveform vector analysis, and on-site current calibration to precisely locate a high-resistance short-circuit fault between the B and C phases of the 9SD high-current switching terminal within the T032 switch control cabinet. The root cause was identified as residual copper wire and accumulated dirt within the terminal screw holes, resulting in high-resistance discharge between Phases B and C. Key factors contributing to the residual copper wire—including excessive operation frequency, copper material properties, and manufacturing defects—were analyzed, and targeted operational and maintenance improvement measures as well as accident prevention strategies were proposed. These research findings provide important references for identifying potential hazards in secondary circuits and managing the operation and maintenance of high-current terminals at ultra-high-voltage substations.

     

/

返回文章
返回