ZS1型中压开关柜触头过热原因查找及建议措施
Investigation and Suggestions for the Overheating of Contacts in ZS1 Type Medium Voltage Switchgear
-
摘要: 某电站在检修时发现厂用电源进线开关柜触头呈灰黑色,有明显过热痕迹,通过检查和分析,发现开关柜静触头与断路器触指镀银层被硫化,导致接触电阻超标并严重发热运行。在去除静触头表面硫化层和更换断路器触指后,接触电阻恢复正常,本文结合工程实践,对导体镀银层被硫化的应对措施提出一些建议,供同行借鉴。Abstract: During overhaul of a power station,it was found that the contacts of the power supply incoming line switch cabinet were grey-black and showed obvious signs of overheating.Through inspection and analysis,it was discovered that the silver plating on the static contacts of the switchgear and the contact fingers of the circuit breaker had been sulfidized, leading to excessive contact resistance and overheating.After removing the sulfidized layer on the static contact surface and replacing the contact fingers of the circuit breaker,the contact resistance returned to normal.This paper proposes some suggestions for dealing with the sulfidation of conductive silver plating on engineering practice,which can be referred to by peers.