高级检索

一起35kV开关柜高阻接地故障的综合诊断与隐蔽性试验验证

Comprehensive Diagnosis of a 35 kV Switchgear High-impedance Grounding Fault and Experimental Verification of Its Concealment

  • 摘要: 某地铁110kV变电站35kV开关柜发生持续47分钟电压异常,诊断为C相铜排螺栓松动导致高阻接地,故障电流低于定值,保护未动作,暴露保护死区。联合厂家开展模拟试验:徒手拧紧时接触电阻为标准力矩数倍至十倍;630A电流下通电10h,接触不良点温差仅2~4K,远低于温度异常门槛值;烧损套管在气室中局放仅0.06pC,仍合格。证明缺陷潜伏期隐蔽性极强,常规手段难以识别。建议地铁新线建设时重点审查开关柜安装后的回路电阻测试数据,建立电压趋势报警机制。

     

    Abstract: A 47-minute voltage anomaly occurred in the 35 kV switchgear of a 110 kV substation in a metro system. The fault was diagnosed as high-impedance grounding caused by a loose C-phase copper busbar bolt. The fault current remained below the protection setting, and no trip was triggered, exposing a protection dead zone. A simulation test was conducted jointly with the switchgear manufacturer. The test results showed that the contact resistance under hand-tightened condition was several to ten times that under standard torque. Under a 630 A current for 10 hours, the temperature difference at the poor-contact point was only 2–4 K, far below the temperature anomaly threshold. The damaged bushing had a partial discharge value of only 0.06 pC in an gas compartment and still met the acceptance criteria. These results confirm that such contact defects are extremely difficult to detect by conventional means during the incubation period. It is recommended that loop resistance test data after switchgear installation be reviewed during the construction of new metro lines and that a voltage trend alarm mechanism be established.

     

/

返回文章
返回