金华换流站极Ⅰ高端Y/ΔA相换流变,额定容量为382000kVA、变比510/√3:161.8kV、冷却方式ODAF。换流变压器铁心采用单相四柱结构,两芯柱两旁轭铁心与绕组位置关系示意及换流变器身结构如图1、2所示。

Analysis of Abnormal Dielectric Loss of Grid Side Winding of a 600kV Converter Transformer in Converter Station

  • 摘要: 针对某极Ⅰ高端600kV换流变网侧绕组对阀侧绕组及对地介损异常增大事件,建立了换流变内部各部件间分布电容等效模型;依托针对换流变介损异常的T型网络模型分析、铁心与夹件介损的隔离测试,以及网侧、阀侧绕组相关介损与电容量的解耦计算,完成该换流变网侧绕组介损超标成因的定性研判与定量分析。辅以现场器身加温处理及频域介电谱检测试验,证实此次介损异常是由换流变网侧绕组对铁心部位受潮劣化、绝缘性能下降所致。

     

    Abstract: Aiming at the abnormal increase of the dielectric loss of the grid-side winding to the valve-side winding and to the ground of a pole I high-end 600 kV converter transformer, established the distributed capacitance equivalent model between the internal components of the converter transformer. Meanwhile based on the analysis of the T-type network model for the abnormal dielectric loss of the converter transformer, the dielectric loss isolation test of the core and the clamp, and the decoupling calculation of the related dielectric loss and capacitance of the grid-side and valve-side windings, the qualitative analysis and quantitative analysis of the causes of the excessive dielectric loss of the grid-side winding of the converter transformer are completed. With the help of body heating treatment and frequency domain dielectric spectrum detection test, it is confirmed that the abnormal dielectric loss is caused by the damp deterioration and insulation degradation of the converter transformer grid-side winding to the core.

     

/