使用柴油发电机的主变一次升流试验

Primary Current Injection Test of Main Transformer Using Diesel Generator

  • 摘要: 对使用柴油发电机进行400kV主变一次升流试验,分别对高压侧注入低压侧短接、低压侧注入高压侧短接、以及低压1侧注入低压2侧短接三种试验接线方式下,采用有名值和标幺值两种方法进行理论计算分析。通过项目现场实测验证,该试验方案可有效校验主变各侧保护、计量及测量装置的电流二次回路接线的准确性,同时在验证主变分相差动保护回路的基础上,进一步核实了主变高、低压侧零序差动保护电流二次回路的正确性,可为400kV主变交接验收试验及设备安全稳定运行提供技术参考。

     

    Abstract: A primary current injection test was carried out on the 400kV main transformer using a diesel generator. Theoretical calculations and analyses based on actual value and per-unit value principles were performed respectively under three test wiring configurations: injecting current on the high-voltage side with the low-voltage side short-circuited, injecting current on the low-voltage side with the high-voltage side short-circuited, and injecting current on Low-Voltage Side 1 with Low-Voltage Side 2 short-circuited. Actual on-site testing of the project verified the correctness of the secondary current circuits for protection, metering and measurement on all sides of the main transformer. In addition to the phase-separated differential protection of the main transformer, the secondary current circuits for zero-sequence differential protection on both the high-voltage and low-voltage sides of the main transformer were also validated. It provides a technical reference for hand-over-acceptance tests and safe-stable operation of 400?kV main transformers.

     

/