高级检索

基于低压法兰屏蔽的MOA 测量方法

DONG Zhe1, XX1, XX1, ZOU Yuan2, LIU Xiaofei22.State Grid Hebei Extra Voltage Company,Shijiazhuang Hebei 050070, China)

  • 摘要: 受杂散电流影响,采用不拆一次引线方法测量多节结构MOA下节时,测量结果误差大。通过实验确定了杂散电流的来源,并实测了杂散电流的大小。基于此提出采用在低压法兰表面加屏蔽的方法屏蔽杂散电流,减少测量误差。最后通过现场试验验证了低压屏蔽法兰电流法的可行性。

     

    Abstract: : Due to the influence of stray current, when measuring the lower section of a multi-section MOA without disconnecting the primary leads, the measurement results exhibit significant errors. Through experiments, the source of stray current was identified, and its magnitude was measured. Based on this, it is proposed to adopt a method of adding a shield on the surface of the low-voltage flange to shield the stray current and reduce measurement errors. Finally, the feasibility of the low-voltage shielded flange current method was verified through field tests.

     

/

返回文章