高级检索

一起电流互感器二次侧螺钉接触不良导致电流异常的案例分析

A Case Analysis of Abnormal Current Caused by Poor Screw Contact on the Secondary Side of a Current Transforme

  • 摘要: 本文针对一起10 kV高压专变用户三相三线电能表出现的电流异常现象,A、C两相电流幅值持续差异显著而波动趋势高度同步,开展了系统的故障诊断与机理分析。通过用电信息采集系统监测与现场逐级排查,定位故障原因为C相电流互感器二次回路接线端子存在螺钉虚拧,导致接触电阻显著增大,并使二次电流采样值降至实际值的约1/3。本文结合电流互感器端子结构、等效电路模型,理论分析了接触电阻增大对二次电流的影响,阐明紧固扭矩不足是引发接触可靠性下降的关键因素。在此基础上,从施工安装、验收投运、运行监测及管理保障四个方面提出了预防性措施与标准化建议。本案例为高压计量装置类似电流异常情况的诊断与消缺提供参考。

     

    Abstract: This paper conducts a systematic fault diagnosis and mechanism analysis regarding a current abnormality observed in a three-phase three-wire energy meter for a 10 kV high-voltage dedicated transformer user. The anomaly was characterized by a significant persistent difference in the current amplitudes between phases A and C, while their fluctuation trends remained highly synchronized. Through monitoring via the electricity consumption information acquisition system and on-site step-by-step troubleshooting, the root cause was identified as a loose screw fastening at the wiring terminal of the secondary circuit for phase C current transformer. This led to a significant increase in contact resistance, reducing the sampled secondary current to approximately one-third of its actual value. By analyzing the terminal structure of the current transformer and its equivalent circuit model, this paper theoretically examines the impact of increased contact resistance on the secondary current and clarifies that insufficient tightening torque is the key factor causing the degradation of contact reliability. Furthermore, preventive measures and standardized recommendations are proposed from four aspects: construction and installation, acceptance and commissioning, operation monitoring, and management safeguards. This case provides a reference for the diagnosis and rectification of similar current abnormalities in high-voltage metering devices.

     

/

返回文章
返回