高级检索

一起500kV变电站压变二次回路异常事例分析

Analysis of an Abnormal Case in the Secondary Circuit of aTransformer

  • 摘要: 通过分析一起500kV变电站压变二次回路异常事例,发现若压变二次回路的接地点在保护室时,一旦压变二次回路发生单相接地,将会在相关二次回路中出现短路环流,该环流会使得其它电压二次回路的N600对地发生电位偏移,从而导致其它运行装置的电压采集异常而出现告警信号,最后得出了独立的、与其他电压互感器二次回路没有电气联系的二次回路宜在开关场地就地一点接地的结论。

     

    Abstract: By analyzing an abnormal case of the secondary circuit of a 500kV substation , it was found that if the grounding point of the secondary circuit of the voltage transformer is in the protection room, once a single-phase grounding occurs in the secondary circuit of the voltage transformer, a short-circuit circulating current will appear in the relevant secondary circuit. This circulating current will cause a potential shift of N600 to ground in other voltage secondary circuits, resulting in abnormal voltage collection of other operating device and an alarm signal. Finally, it was concluded that independent secondary circuits without electrical connection with other voltage transformer secondary circuits should be grounded locally at one point in the switch yard.

     

/

返回文章
返回