敞开式变电站电流互感器异常振动问题分析与诊断

Analysis and Diagnosis of Abnormal Vibration of Current Transformer in Open-type Substation

  • 摘要: 电流互感器是敞开式变电站关键一次设备,二次回路断线易引发过电压、保护拒动等严重事故。以某220kV敞开式变电站110kV LCWB6—110W2型油浸式电流互感器异常振动、二次断线故障为案例,结合现场试验、X射线检测和解体解剖,查明故障根源为二次引线焊锡连接存在先天虚焊缺陷,在长期电磁振动、温度循环作用下焊点持续劣化,最终引发回路断线。根据故障机理,提出老旧焊锡工艺电流互感器专项排查方案,为同类设备隐患治理提供参考。

     

    Abstract: Current transformer (CT) is key primary equipment in open-type substations. Breakage of the secondary circuit may easily trigger severe accidents such as overvoltage and protection failure to operate. Taking the abnormal vibration and secondary circuit breakage fault of LCWB6—110W2 oil-immersed current transformer at the 110 kV bay of a 220 kV substation as a case study, combined with on-site tests, X-ray inspection and disassembly analysis, it is identified that the root cause of the fault lies in inherent cold solder joint defects of the soldered connection for secondary leads. The solder joints degrade continuously under long-term electromagnetic vibration and temperature cycling, eventually resulting in circuit breakage. According to the fault mechanism, a special inspection scheme for current transformers adopting the aging soldering process is proposed, which provides a reference for hidden danger treatment of similar equipment.

     

/