高级检索

基于DCS运行数据的火电机组一次调频响应特性分析及优化控制方法

Analysis of Primary Frequency Regulation Response Characteristics and Optimization Control Method of Thermal Power Units Based on DCS Operation Data

  • 摘要: 为提升火电机组一次调频响应能力,基于DCS运行数据,对频率扰动过程中的电网频率、有功功率、调门开度、主汽压力、DEH指令和AGC指令等变量进行分析。结合典型扰动过程,提取响应延迟时间、最大负荷变化量、负荷变化速率和稳定时间等指标,分析一次调频响应不足的主要原因,并从参数整定、DEH调门响应优化、AGC与CCS协调控制等方面提出改进方法。结果表明,优化后机组响应延迟时间由8.2 s缩短至4.6 s,最大负荷变化量由12.5 MW提高至17.8 MW,一次调频合格率由86.0%提高至95.5%,机组调频响应速度和运行稳定性得到改善。

     

    Abstract: In order to improve the primary frequency regulation response capability of thermal power units, DCS operation data were used to analyze key variables during frequency disturbance, including grid frequency, active power, valve opening, main steam pressure, DEH command and AGC command. Based on a typical disturbance process, response delay time, maximum load variation, load change rate and stabilization time were extracted to evaluate the primary frequency regulation performance. The main causes of insufficient response were analyzed, and optimization measures were proposed from the aspects of parameter setting, DEH valve response optimization, and coordinated control of AGC and CCS. The results show that after optimization, the response delay time is reduced from 8.2 s to 4.6 s, the maximum load variation increases from 12.5 MW to 17.8 MW, and the qualified rate of primary frequency regulation increases from 86.0% to 95.5%. The response speed and operation stability of the unit are effectively improved.

     

/

返回文章
返回