高级检索

厂区新增工艺段10kV配电室及工艺生产区域接地系统设计

Design of grounding system for 10kV distribution room and process production area in the newly added process section of the factory area

  • 摘要: 随着“双碳”目标的推进与工业升级需求,传统电力企业需在现有厂区内增建低碳化、自动化工艺段,并配套建设相应的供电与接地系统。以火电厂区新增碳捕集(CCUS)工艺段作为实例,系统且全面地阐述了其配套10kV配电室及工艺生产区域的接地系统设计。设计充分结合原有厂区220kV主接地网的实际情况,采用分层、分区的接地策略,进而提出独立接地网构建、等电位网格延伸以及多路径主网互联的综合设计方案。重点论述了接地网结构参数选型、接地电阻计算与控制、工艺区等电位联结措施、新旧接地系统互联技术要点等内容。该方案已通过现场实施与测试验证,接地电阻满足GB 50065-2011要求,全厂接地电位均衡性良好,为类似厂区扩建项目的接地系统设计提供了完整、可靠的技术路径。

     

    Abstract: With the promotion of the "dual carbon" goal and the demand for industrial upgrading, traditional power companies need to build low-carbon and automated process sections within their existing factory areas, and provide corresponding power supply and grounding systems. Taking the newly added carbon capture (CCUS) process section in a thermal power plant as an example, this paper systematically and comprehensively elaborates on the grounding system design for its supporting 10kV distribution room and process production area. The design fully combines the actual situation of the existing 220kV main grounding grid in the factory area, adopts a layered and partitioned grounding strategy, and proposes a comprehensive design scheme for independent grounding grid construction, equipotential grid extension, and multi-path main grid interconnection. The focus is on the selection of grounding grid structural parameters, calculation and control of grounding resistance, equipotential bonding measures in process areas, and key points of interconnection technology between new and old grounding systems. The scheme has been implemented and tested on site, and the grounding resistance meets the requirements of GB 50065-2011. The grounding potential balance of the entire plant is good, providing a complete and reliable technical path for the design of grounding systems for similar plant expansion projects.

     

/

返回文章
返回