10 kV双切换柜及开闭所备自投装置未启动原因分析

Analysis on the Failure of Automatic Bus Transfer Device to Activate in a 10 kV Dual-switch Cabinet and Switching Station

  • 摘要: 以某10 kV双切换柜及开闭所发生故障时备自投装置未启动为例,通过分析运行方式、充放电逻辑、闭锁条件、保护定值、录播数据及事件记录等,明确备自投装置充电逻辑有重大缺陷,存在较大的保护盲区,并针对保护定值提出相应的改进措施。

     

    Abstract: This paper takes the failure of the automatic bus transfer (ABT) device to operate during a fault in a 10 kV dual-switch cabinet and switching station as an example. A comprehensive analysis is conducted on the operation mode, charging/discharging logic, blocking conditions, protection setting values, fault recording data and event records of the device. The results show that the charging logic of the ABT device has significant defects, which creates a large protection blind zone. Corresponding improvement measures for the protection setting values are proposed accordingly.

     

/