高级检索

一起开关柜异常报警事件的分析与处理

Analysis and Handling of an Abnormal Alarm Event in a Switchgear

  • 摘要: 针对某配电所10 kV高压开关柜在实际运行过程中频繁报"控制回路断线"告警的现象,结合系统运行方式与二次回路原理图展开分析,发现异常告警源于二次回路设计缺陷:合闸闭锁触点误接入跳闸监视回路导致系统状态误判。在明确缺陷成因的基础上,提出了解决措施,包括调整合闸闭锁触点接入位置和优化运维策略,并建议加强运维人员技术培训与图纸审核,以提升系统可靠性与安全性。

     

    Abstract: This paper addresses the frequent "control circuit break" alarms in a 10 kV high-voltage switchgear at a distribution substation during actual operation. By analyzing the system's operational mode and the secondary circuit schematic, it was determined that the abnormal alarms originated from a design defect in the secondary circuit: The closing lockout contact was incorrectly wired into the trip position monitoring circuit, leading to misinterpretation of the system status. Based on identifying the root cause, improvement measures are proposed, including modifying the contact wiring position and optimizing operation and maintenance strategies, it is also recommended to enhance technical training for maintenance personnel and strengthen the review of circuit diagrams to improve system reliability and safety.

     

/

返回文章
返回