特高压换流站500 kV站用变保护误动作分析
Analysis on Maloperation of 500 kV Station Transformer Protection in UHV Converter Station
-
摘要: 分析了特高压换流站500 kV站用变保护电流二次回路短路导致区外故障时保护不正确动作的案例,结合故障录波图和保护回路检查,对保护不正确动作的原因进行了分析、推理和验证,确认了电流二次回路的故障点,并对站用变保护相关工作提出了具体的建议。Abstract: This paper analyzes a incorrect protection operation that the secondary current circuit short-circuit of the 500 kV station transformer protection in an UHV converter station. By combining fault recording waveform diagrams and protection circuit inspection, the causes of incorrect protection operation were analyzed, reasoned, and verified. The fault point in the secondary current circuit was identified. The corresponding advice of the parameter setting put forward in this paper.