一种35 kV交流电抗器过电压治理方案研究及应用

A Study on the Overvoltage Control Scheme for 35 kV AC Reactors and Its Application

  • 摘要: 针对35 kV交流电抗器投切过电压及传统阻容保护装置易老化问题,提出一种新型非线性阻容保护方案。其核心是将传统阻容装置的定值电阻替换为氧化锌压敏电阻,并适配金属氧化物避雷器,实现正常工况隔离、过电压动态接入。现场试验表明,该装置可有效抑制电抗器退出时的电压振荡,且解决了传统装置易老化缺陷,为35 kV交流电抗器过电压防护提供可行技术方案,具有一定工程应用价值。

     

    Abstract: Aiming at the switching overvoltage of 35 kV AC reactors and the aging problem of traditional resistance-capacitance (RC) protection devices, this paper proposes a new type of nonlinear RC protection scheme. The core of the scheme is to replace the fixed resistor of the traditional RC device with a zinc oxide varistor and adapt it to the metal oxide surge arrester, so as to realize the isolation of the device under normal operating conditions and dynamic connection when overvoltage occurs. Field tests show that the device can effectively suppress the voltage oscillation when the reactor is disconnected, solves the aging defect of traditional devices, provides a feasible technical solution for 35 kV reactor overvoltage protection, and has certain engineering application value.

     

/