10 kV接地故障造成消弧装置跳闸案例分析

Case Analysis of Arc Suppression Device Tripping Caused by 10 kV Grounding Fault

  • 摘要: 某10 kV馈线发生C相接地故障时,运行于同段10 kV母线的消弧装置开关柜由于CT接线方式与保护装置定值整定不相配合而跳闸。从站内消弧装置结构、事故过程的报文分析和故障录波波形、定值整定等方面剖析案例,并提出解决方案。

     

    Abstract: When a C-phase ground fault occurred on a 10 kV feeder line, the arc suppression device switchgear operating on the same 10 kV busbar tripped due to the mismatch between the current transformer wiring method and the protection device setting. The paper analyzes the case from the aspects of the structure of the on-site arc extinguishing device, message analysis of the accident process, fault waveform recording, and setting of the fixed value, and proposes solutions.

     

/