高级检索

站用交流电源系统保护配置及优化方案

An Enhanced Protection Configuration and Optimization Scheme for Auxiliary AC Power Supply System

  • 摘要: 站用交流电源保护系统对于用电设备的供电可靠性至关重要,不合理的保护配置及定值失配可能会造成事故影响扩大,甚至影响全站供电。分析了现有站用交流电源系统保护的配置情况,明确了现有保护配置方案存在定值整定配合困难,过流保护动作时间存在优化空间的问题。为此,提出了一种站用电交流电源系统反时限电流保护优化配置方案,利用电压系数修正反时限过流保护,在简化定值整定的同时,可提升站用交流电源系统保护的速动性与可靠性,为现场运行人员提供有益参考。

     

    Abstract: The protection system of station AC power supply is crucial to the power supply reliability of electrical equipment. Unreasonable protection configuration and setting mismatch may lead to accident escalation, affecting the power supply of the entire station. This paper analyzes the current protection configuration of station AC power supply systems, identifies issues such as difficulties in coordination of setting values and room for optimization in the operating time of overcurrent protection. An optimized configuration scheme for inverse-time overcurrent protection in station AC power supply systems is proposed, which uses voltage coefficients to modify the inverse-time overcurrent protection. This approach simplifies setting value coordination while improving the speed and reliability of station AC power supply system protection, providing valuable reference for field operators.

     

/