变压器绝缘性能测试技术在变电站调试过程中的应用研究

Research on Transformer Insulation Performance Testing Technology During Substation Debugging Process

  • 摘要: 探讨变电站调试中变压器绝缘性能测试技术方案。针对套管末屏接地不良、绝缘油劣化等典型缺陷,采用绝缘电阻分段测量与多频段tanδ扫描为核心检测手段。通过ZC-90测试仪获取的极化指数(PI=R600s/R60s)精准定位末屏接触电阻异常,配合QS30介损仪在50~200 Hz频段检测,发现油中中等极性杂质导致频散率达20%。处理措施包括更换弹簧触指接地结构、实施双级真空+膜过滤组合工艺,使接触电阻降至45 mΩ,微水含量降至8ppm。泄漏电流阶梯升压测试显示0.8Un时电流异常攀升,通过注入BHT抗氧化剂及布设分布式光纤测温系统,有效控制介质老化进程。

     

    Abstract: Discussion on the technical scheme for testing the insulation performance of transformers in substation commissioning. For typical defects such as poor grounding of the casing end screen and deterioration of insulation oil, insulation resistance segmented measurement and multi frequency tan δ scanning are adopted as the core detection methods. The polarization index(PI=R600s/R60s) obtained through the ZC-90 tester was used to accurately locate the abnormal contact resistance of the end screen. Combined with the QS30 dielectric loss meter, it was detected in the frequency range of 50~200 Hz that the medium polarity impurities in the oil caused a dispersion rate of 20%. The handling measures include replacing the spring contact finger grounding structure and implementing a dual stage vacuum+membrane filtration combination process to reduce the contact resistance to 45 mΩ and the micro water content to 8ppm. The leakage current step up test showed an abnormal increase in current at 0.8Un. By injecting BHT antioxidant and distributed fiber optic temperature measurement system, the aging process of the medium was effectively controlled.

     

/