高级检索

基于超声波检测的110~220 kV高压电缆接头热缺陷诊断技术研究

Research on Thermal Defect Diagnosis Technology of 110~220 kV High Voltage Cable Joint Based on Ultrasonic Detection

  • 摘要: 针对110~220 kV高压电缆接头热缺陷诊断难题,提出一种基于超声波检测的诊断方法。通过超声波传播特性分析实现缺陷预定位,采用层析成像技术进行精确定位与成像,结合特征参数提取进行定量评估。实验结果表明,该方法可有效识别电缆接头的热损伤状态,热损伤接头的声速降至2085 m/s,反射波幅值升至-21.3 dB,衰减系数达2.23 dB/(mm·MHz),为评估电缆接头劣化程度提供了可靠依据。

     

    Abstract: This article proposes a new diagnostic method based on ultrasonic testing to address the difficulty of diagnosing thermal defects in 110~220 kV high-voltage cable joints. Defect pre positioning is achieved through analysis of ultrasonic propagation characteristics, and precise positioning and imaging are carried out using tomographic imaging technology, combined with feature parameter extraction for quantitative evaluation. The experimental results show that this method can effectively identify the thermal damage state of cable joints. The sound velocity of the thermal damage joint decreases to 2085 m/s, the reflected wave amplitude increases to -21.3 dB, and the attenuation coefficient reaches 2.23 dB/(mm·MHz), providing a reliable basis for evaluating the degree of degradation of cable joints.

     

/

返回文章
返回