高级检索

一起110 kV变压器故障原因分析

Cause Analysis of A 110 kV Transformer Failuer

  • 摘要: 针对一起110 kV变压器高压套管存在缺陷导致跳闸故障的原因进行分析。通过对变压器进行绝缘电阻测量、直流电阻测量、油色谱分析等诊断性电气试验,并结合返厂解体检查情况,确认故障原因为该变压器高压侧C相套管油纸电容芯体末端存在缺陷。高压套管电容屏的绝缘强度因耐受不住施加电压,导致套管与变压器上铁轭放电,造成套管下部瓷套破裂,使套管底部与变压器铁轭再次放电。

     

    Abstract: This article analyzes the cause of a tripping fault triggered by a defect in the high-voltage bushing of a 110 kV transformer. Through diagnostic electrical tests such as insulation resistance measurement, DC resistance measurement, and oil chromatography analysis on the transformer, combined with the results of the factory disassembly inspection, it was confirmed that the cause of the failure was a defect in the end of the oil-paper capacitor core of the C-phase bushing on the high-voltage side of the transformer. The insulation strength of the bushing capacitive screen cannot withstand the applied voltage, leading to discharge between the bushing and the transformer′s upper iron yoke. This causes the lower porcelain sleeve of the bushing to crack, resulting in further discharge between the bottom of the bushing and the transformer′s iron yoke.

     

/

返回文章
返回