基于容性负荷工况下电压断相故障对计量的影响分析

Analysis of the Impact of Voltage Phase Failure on Metering Under Capacitive Load Conditions

  • 摘要: V/V-12接线电压互感器在中性点不接地和经高阻抗接地系统中运用广泛,通常用于10 kV高供高计用户计量,电压互感器出现断相故障时引起计量差错,存在计量失准、供电服务投诉等风险。结合采用V/V-12接线电压互感器的10 kV高供高计用户,运行过程中电压断相故障引起电量异常,分析故障前后采集系统曲线数据的变化规律,结合负荷性质计算退补电量,提出详细的防范措施,有效防范各种风险。

     

    Abstract: The V/V-12 wiring voltage transformer is widely used in neutral ungrounded and high impedance grounded systems. It is usually used for metering by 10 kV high supply and high meter users. When the voltage transformer experiences a phase failure, it may cause metering errors, leading to risks such as inaccurate metering and power supply service complaints. This article combines the 10 kV high supply and high meter users who use V/V-12 wiring voltage transformers. During operation, voltage phase failure caused abnormal power consumption. The change law of the collected system curve data before and after the fault is analyzed. Combined with the nature of the load, the refund and compensation power is calculated, and detailed preventive measures are proposed to effectively prevent various risks.

     

/