220kV Ⅱ香苏线风偏跳闸的研究分析

Cause Analysis of Wind Deflection Trip of 220 kV Ⅱ Xiangshan-Suyuan Line

  • 摘要: 对220 kV Ⅱ香苏线故障跳闸情况进行了介绍,初步分析跳闸是因为大风天气导致合成绝缘子串发生偏移、空气间隙被击穿,结合线路运行的实际情况对风偏进行了校验分析,并针对微地形和微气象区域下、同一输电通道的2条或多条平行输电线路的防风偏问题,提出了具体的改进措施和建议,为微地形、微气候条件下输电线路的防风偏处理提供了借鉴和参考。

     

    Abstract: An introduction was made to the situation of the trip of the 220 kV II Xiangshan-Suyuan power supply line, and the preliminary analysis indicated that the trip was caused by the deviation of the composite insulator string and the breakdown of the air gap due to strong winds. Combining with the actual operation of the line, a verification analysis of wind deviation was carried out. Specific improvement measures and suggestions were proposed for the wind deviation issues of two or more parallel transmission lines in the same transmission channel in the micro-terrain and micro-meteorological areas, providing reference for handling wind deviation of transmission lines under micro-terrain and micro-climate conditions.

     

/